Propane generator not getting fuel. Hoping someone might have an idea where I go from here.

onanysunday

Well-known member
Joined
May 7, 2021
Messages
3,592
Reaction score
3,389
So my generator has not been working for a good year or so and I had not done anything with it until now. Getting ready to sell the coach. The generator is a generac np-66g. I replaced the regulator at the propane tank and I have verified I have propane getting to what looks like a couple of regulators or I don't know what to allow the propane into the carb. I checked spark and that was good. Used a little starting fluid and the generator starts right up. So it is a fuel delivery problem for sure.
 

Attachments

  • 20250707_102939.jpg
    20250707_102939.jpg
    3.2 MB · Views: 3
  • 20250712_090422.jpg
    20250712_090422.jpg
    3.7 MB · Views: 3
The propane first goes into this deal. It has two wires going into it. It has a plastic cap that pops off and it slides off of a pin.
 

Attachments

  • 20250712_090433.jpg
    20250712_090433.jpg
    3.1 MB · Views: 3
  • 20250712_090730.jpg
    20250712_090730.jpg
    2.9 MB · Views: 3
  • 20250712_090753.jpg
    20250712_090753.jpg
    3 MB · Views: 3
After that the propane goes through this unit.
 

Attachments

  • 20250712_090517.jpg
    20250712_090517.jpg
    3.4 MB · Views: 3
  • 20250712_090507.jpg
    20250712_090507.jpg
    3.2 MB · Views: 3
  • 20250712_090448.jpg
    20250712_090448.jpg
    1.6 MB · Views: 3
Then from there the propane goes through a rubber hose into the carb. If I had to guess I would say the carb is not the issue but not sure what to look at or check here.
 

Attachments

  • 20250712_091037.jpg
    20250712_091037.jpg
    3.9 MB · Views: 1
  • 20250712_091047.jpg
    20250712_091047.jpg
    3.5 MB · Views: 1
Is there 12VDC to the solenoid valve when cranking/on?
Yes 12 volts on one side when cranking. When you stop cranking it takes another second and then power goes out. Then I can feel that solenoid click.
 